Diagnostics
4.1 Diagnostics via LEDs
4.1.2.4

Smart Line Modules booksize 5 kW and 10 kW

Table 4- 17
Meaning of the LEDs at the Smart Line Modules 5 kW and 10 kW
LED
Color
State
READY
Off
Green
Continuous
light
Yellow
Continuous
light
Red
Continuous
light
DC LINK –
Off
Yellow
Continuous
light
Red
Continuous
light
4.1.2.5

Smart Line Modules booksize 16 kW to 55 kW

Table 4- 18
Meaning of the LEDs at the Smart Line Modules ≥ 16 kW
State
Ready
DC link
Off
Off
Green
Off
Orange
Red
Orange
Orange
Red
Green / red
flashing light
0.5 Hz
318
Description, cause
Electronic power supply is missing or outside permissi-
ble tolerance range.
Component is ready to operate.
Pre-charging not completed.
Bypass relay dropped out
EP terminals not supplied with 24 VDC.
Overtemperature
Overcurrent
Electronic power supply is missing or outside permissi-
ble tolerance range.
DC link voltage within permissible tolerance range.
DC link voltage outside permissible tolerance range.
Line supply fault.
Description, cause
Electronic power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
LED is controlled irrespective of the corresponding messag-
es being reconfigured.
Firmware is being downloaded.
Remedy
Check the line voltage
Remedy and acknowledge
fault
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Remedy
Diagnose fault (via output
terminals) and
acknowledge it (via input
terminal)
Check the line voltage.