Relay Outputs X542; Description Of The Leds On The Terminal Module 31 (Tm31) - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

7.2.3.12

Relay outputs X542

Table 7-15
Terminal block X542
Terminal
1
2
3
4
5
6
Max. cross-section that can be connected 2.5 mm
Type: Screw terminal 3 (see Appendix A)
1) DO: digital output, NO: normally-open contact, NC: normally-closed contact, COM: Mid-position contact
7.2.3.13

Description of the LEDs on the Terminal Module 31 (TM31)

Table 7-16
Description of the LEDs on the TM31
LED
Color
-
Green
Orange
RDY
Red
Green/
Red
Green/
Orange
or
Red/Orange
Equipment Manual AC Drive
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0
Supplementary system components and encoder system integration
Designation
1)
DO 0.NC
DO 0.COM
DO 0.NO
DO 1.NC
DO 1.COM
DO 1.NO
2
State
Description
OFF
Electronics power supply is missing or outside permissible tolerance
range.
Steady light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Steady light
DRIVE-CLiQ communication is being established.
At least one fault is present in this component. Note:
LED is driven irrespective of the corresponding messages being
Steady light
reconfigured.
Flashing light
Firmware is being downloaded.
2 Hz
Detection of the components via LED is activated (p0154).
Note:
Flashing light
Both options depend on the LED status when module recognition is
2 Hz
activated via p0154 = 1.
Technical specifications
Contact type: Two-way contact max. load current: 8 A
Max. switching voltage: 250 V
Max. switching power at 250 V
Max. switching power at 250 V
Max. switching power at 30 V
Required minimum current: 100 mA
Overvoltage category: Class III to EN 60 664-1
7.2 Terminal Module 31 (TM31)
, 30 V
AC
DC
: 2000 VA (cosϕ = 1)
AC
750 VA (cosϕ = 0.4)
AC:
: 240 W (ohmic load)
DC
7-15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents