Diagnostics

7.14 LEDs on the TM54F Terminal Module

7.14
LEDs on the TM54F Terminal Module
Table 7- 19
Description of the LEDs on the Terminal Module TM54F
LED
Color
-
Green
Orange
Red
READY
Green / Red
Green /
Orange
or
Red / Orange
7.15

LEDs on the SITOP power supply unit

Table 7- 20
LED
Green
Yellow
Red
328
State
off
The electronics power supply is missing or outside the permissible tolerance
range.
Steady light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Steady light
DRIVE-CLiQ communication is being established.
Steady light
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the corresponding messages
have been reconfigured.
0.5 Hz
Firmware is being downloaded.
flashing light
2 Hz flashing
Firmware download is complete. Waiting for POWER ON
light
Flashing light Detection of the components via LED is activated (p0154).
Note:
Both options depend on the LED status when module recognition is
activated via p0154 = 1.
Meaning of the LEDs on the SITOP power supply unit
Meaning
Output voltage > 20.5 V
Overload, output voltage < 20.5 V ("constant current" mode)
Latching shutdown ("Shutdown" mode)
Description