Commissioning
3.8 First commissioning vector control AC drive blocksize format
Procedure
8.
p0100 = 0
9.
p03XX[0] = ...
10.
p1900 = 2
11.
p0010 = 0
RDY is lit red, fault F07085 signals that a control parameter has been changed.
Parameter p0840[0] can only be changed with access level p0003 = 3.
12.
p0840[0] =
r0019.0(DO 1)
13.
p1035[0] =
r0019.13 (DO 1)
158
IEC/NEMA motor standard
0 IEC motor (SI units, e.g. kW)
Preset:
Rated motor frequency (p0310): 50 Hz
Specification of the power factor cos φ (p0308)
1 NEMA motor (US units, e.g. hp)
Preset:
Rated motor frequency (p0310): 60 Hz
Specification of the efficiency (p0309)
Note:
When p0100 is changed, all the rated motor parameters are reset.
Rated motor data [MDS]
Only when p0300 < 100 (third-party motor)
Enter the rated motor data in accordance with the type plate, e.g.
p0304[0] Rated motor voltage [MDS]
p0305[0] Rated motor current [MDS]
p0307[0] Rated motor output [MDS]
p0308[0] Rated motor power factor [MDS] (only when p0100 = 0)
p0309[0] Rated motor efficiency [MDS] (only when p0100 = 1)
p0310[0] Rated motor frequency [MDS]
p0311[0] Rated motor speed [MDS]
p0335[0] Motor cooling type [MDS] *
0: Natural cooling
1: Forced cooling
2: Water cooling
Motor data identification and rotating measurement
0 Inhibited
1 Motor data identification for rotating motor
2 Motor data identification for a stationary motor
Message A07991 is displayed, motor data identification has been activated.
Drive commissioning parameter filter
0 Ready
1 Quick commissioning
BI: ON/OFF1 [CDS]
Sets the signal source for STW1.0 (ON/OFF1)
Interconnection with r0019.000 of the drive object Control Unit (DO 1)
Effect: Signal ON/OFF1 from the BOP
BI: Motor potentiometer setpoint higher [CDS]
Sets the signal source to increase the setpoint for the motorized potentiometer
Interconnection with r0019.13 of the drive object Control Unit (DO 1)
Effect: Signal, motorized potentiometer setpoint higher from BOP
Description
1)
1)
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Factory
setting
0
-
2
1
0
0
STARTER Commissioning Manual