Siemens Sinamics s120 Commissioning Manual page 106

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

Commissioning
3.3 STARTER commissioning tool
7. Select the drive unit and call the shortcut menu "Target device > Online access ...".
8. Click the "Module addresses" tab.
Image 3-18
Assigning the IP address and name
Note
When assigning names to IO devices (e.g. a Control Unit) in Ethernet (SINAMICS
components), then ST conventions (Structured Text) must be complied with. The names
must be unique within Ethernet. Other than "-" and ".", no special characters are permitted in
the name of an IO device.
Note
The IP address and device name are stored non-volatile on the memory card of the Control
Unit.
Assigning the IP address using the "Accessible nodes" function
Use the STARTER commissioning tool to assign an IP address and a name for the Ethernet
interface.
1. Connect the Control Unit to the PG/PC.
2. Switch on the Control Unit.
3. Open STARTER.
4. Load your project or create a new project.
106
Setting the online access
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5