4.1.4.6

Terminal Module TM54F

Table 4- 51
Meaning of the LEDs on the Terminal Module TM54F
LED
Color
READY
-
Green
Orange
Red
Green/red
Green / orange
or
Red / orange
L1+, L2+
Red
L3+
Red
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Status
Off
The electronics power supply is missing or outside the
permissible tolerance range.
Continuous
The component is ready for operation, cyclic DRIVE-
light
CLiQ communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
This component has at least one fault.
light
Remark:
The LED is activated irrespective of whether the corre-
sponding messages have been reconfigured.
Flashing light
Firmware is being downloaded.
0.5 Hz
Flashing light 2
Firmware download is complete. Wait for POWER ON.
Hz
Flashing light 1
Component recognition via LED is activated
Hz
(p0154 = 1).
Remark:
Both options depend on the LED status when compo-
nent recognition is activated.
Green / orange: Component is operating without any
faults
Red/orange: Component signals a fault
Off
The controllable sensor power supply is functioning
fault-free.
Continuous
There is a fault in the controllable sensor power supply.
light
Off
The sensor power supply is operating fault-free.
Continuous
The sensor power supply has a fault.
light
Description, cause
Diagnostics
4.1 Diagnostics via LEDs
Remedy
Remedy and
acknowledge
fault or safely
acknowledge
the fault
Carry out a
POWER ON