Booting procedures and booting status changes
In principle, only start and completion are recorded for booting procedures. Booting status
(see r3988) are only recorded when an end status arises that can only be exited by user
action (r3988 = 1, 10, 200, 250, 325, 370, 800). Booting statuses and booting status
changes are:
● POWER ON
● Error in booting (r3988 = 1)
● Fatal error in booting (r3988 = 10)
● Waiting for first commissioning (r3988 = 200)
● Topology error in booting (r3988 = 250)
● Waiting for entry of drive type (r3988 = 325)
● Waiting until p0009 = 0 is set (r3988 = 370)
● Boot status r3988 = <state at which 670 or 680> reached
● Booting finished, cyclic operation
● Reason for new boot < 0 = Internal reason; 1 = Warm start; 2 = Booting from saved data;
3 = Booting after download>
● Drive reset via p0972 = <Mode>
● Partial booting DO started <DO number>
● Partial booting DO <DO number> finished
Commissioning procedures
● Device commissioning: New status p0009 = <new value p0009>
● Commissioning DO <DO number>: New status p0010 = <new value p0010>
● Ram2Rom DO <0 for all DOs> started
● Ram2Rom DO <0 for all DOs> completed
● Project download started
● DO <DO_Number> deactivated
● DO <DO_Number> reactivated
● Component <Component number> deactivated
● Component <Component number> reactivated
● Power Off / Power On required after firmware update (DO <DO number>
Component < Component number >)
● DO <DO-No> deactivated and not available
● Component <component number> deactivated and not available
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Diagnostics
4.3 Diagnostic buffer