Siemens Sinamics s120 Commissioning Manual page 255

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

Parameter
p0607
p4600...p4603
Example: Standard SIMOTICS T-1FW6 built-in torque motors
p4600 0:
p4601 60: PT1000 (or alternatively 20: KTY 84)
p4602 10: PTC fault (PTC 130 °C)
p4603 10: PTC fault (PTC 150 °C)
If you are not using a standard motor, then you must parameterize parameters
p0600...p0606 (see above). Select parameters p4600...p4603 to match the sensor types or
temperature channels of the Sensor Module External SME12x.
Checking the temperature sensors for the Sensor Module External SME12x
In the online mode, you can read out the temperatures of the sensors at the channels of the
Sensor Module External SME12x in parameter r4620[0...3] using the STARTER
commissioning tool.
The maximum motor temperature can also be read in r0035. This parameter indicates the
highest value from parameters r4620[0...3].
For a parameterized PTC sensor type, irrespective of the actual temperature in
r4620, -200° C is always displayed.
The temperature values shown in parameters r0035 or r4620[1] provide information about
whether a parameterized temperature sensor does not match the temperature sensor
actually connected (connection to the wrong temperature sensor):
Parameterized
temperature sensor
KTY 84
PT1000
KTY 84
PT1000
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
3.18 Commissioning SIMOTICS T-1FW6 built-in torque motors
Input
Temperature sensor fault timer
Setting the timer for timing the period between output of the alarm and fault when a
temperature sensor fault is detected.
If a sensor fault has been detected, this timer is started.
If the sensor fault persists when the timer has expired, the relevant fault is output.
Motor temperature sensor 1...4 sensor type
Sets the temperature sensor type for the motor temperature monitoring. Channels 2
... 4 are used for the Sensor Module External SME12x. Channel 1 remains free.
The following values are possible for torque motors:
0: No sensor
10: PTC fault
12: PTC alarm & timer
20: KTY 84
60: PT1000
If you make a selection with timer, you must pre-assign parameter p0606 with the
corresponding timer for a maximum of 2 s.
No sensor
Connected
temperature sensor
PTC
PTC
PT1000
KTY 84
Displayed value in °C
at room temperature 25°C
-40 ... -80 °C
-100 ... -200 °C
+115°C
-100°C
Commissioning