ACCESS LEVEL

A .
A 1 - 0 1 : Parameter Access Level
This setting determines which parameters are
accessible, which are also dependent upon the
setting of the Control Method ( A 1 - 0 2 ) .
The default setting is for Quick-start Access Level,
which accesses 32 parameters. Basic Access
Level allows access to 90 additional parameters.
Advanced Level accesses all parameters available
for a given Control Method setting. The User
Program Access Level will only be available if one
or more parameters are programmed into A 2 - 0 1 through A 2 - 3 2.
See paragraph 4.3 for menu trees for each of the Access Levels, and paragraph 4.5,
Examples 1A and 1B, for programming examples in different Access Levels.
B .
User Program.
to allow a customized Access Level. The drive must first be temporarily set to Advanced
Access Level ( A 1 - 0 4 = 4); then use the "up arrow", "down arrow" and "right arrow" keys
to set A 2 - 0 1 to the first parameter to which access is desired, A 2 - 0 2 to the next, etc.
Only the parameters entered into A 2 - 0 1 through A 2 - 3 2 will be available for monitoring
and modifying if A 1 - 0 1 is then set to "1".
5 . 5
A U T O - R E S T A R T
A .
L 5 - 0 1 : Number of Auto-Restart Attempts
When a fault occurs during operation, the drive can be programmed for an auto-restart
operation to automatically reset the fault. Auto-restart operation will use the number of
reset attempts set in this parameter, up to the maximum of 10. When set to " 0 ", no
auto-restarts will be attempted.
• The following faults can be automatically reset:
OC:
Overcurrent
OV:
Overvoltage
OL3: Overtorque Detect
• The following conditions WILL NOT initiate auto-restart:
1. OL, EF
, PUF or CPF
2.
When OC or UV occurs during deceleration.
3.
When L 2 - 0 1 is programmed to stop during momentary power failure (data =
" 0 "). (See paragraph 5.29, MOMENTARY POWER LOSS RIDE-THRU. )
• The number of restart attempts available will be reset to the L 5 - 0 1 setting when:
1.
10 minutes has elapsed without a fault occurring.
2.
The RESET key, or external Fault Reset push button, is pressed.
3.
Power is removed from the Drive.
Parameters A 2 - 0 1 through A 2 - 3 2 can each be set by the user
fault.
Setting
0
1
2
3
4
GF:
Ground fault
UV1: Undervoltage (Power UV)
5-7
Factory setting: 2
Range: 0 to 4
Description
Monitor Only
User Program
Quick-start
Basic
Advanced
Factory setting: 0
Range: 0 to 10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents