Torque Limit - Veikong gpd 515/g5 Startup Manual

Simplified startup procedure
Table of Contents

Advertisement

5 . 4 5
T O R Q U E LIMIT
The multi-function analog input at terminal 16 may be configured to allow analog control of
the torque limit for both FWD & REV modes. However, the analog reference controls both
FWD torque limit & REV regenerative torque limits.
1R
*
TORQUE
LIMIT
*
1R is a calibration pot only.
NOTE: A minimum priority circuit is associated with the torque limit function,
which means that the lowest value torque limit setting will have priority.
* NOTE: When H 3 - 0 5 is set for " 1 3 ", Terminal 16 is a torque limit ONLY if speed
mode is selected ( d 5 - 0 1 = 0 ). If d 5 - 0 1 = 1 (torque mode), Terminal 16 will be
a torque reference.
The multi-function analog input at terminal 16 may be configured to allow analog control of
the torque limit for both FWD & REV modes. However, the analog reference controls both
FWD & REV torque limits, and the FWD & REV regenerative torque limits.
1R
*
TORQUE
LIMIT
*
1R is a calibration pot only.
NOTE: A minimum priority circuit is associated with the torque limit function,
which means that the lowest value torque limit setting will have priority.
Continued
GPD 515/G5
15 +15V
16 0-10V (20K Ω)
17
C
GPD 515/G5
15 +15V
16 0-10V (20K Ω)
17
C
5-103
Data 1 2 : Regenerative Torque
H3-05 = 12
REGEN
TORQUE
LIMIT
–10V
MULTI-FUNCTION ANALOG INPUT
Data 1 3 * : FWD & REV Torque
Data 1 5 : FWD & REV Torque
H3-05 = 15
100%
TORQUE
LIMIT
0%
0V
–100%
MULTI-FUNCTION ANALOG INPUT
Limit
100%
0%
0V
10V
Limit
Limit
10V