D I G I T A L OPERATOR DISPLAY SELECTION
Exceptions to the general format are as follows:
When setting a value in o1-03, the decimal point position
selected will automatically affect all of the Frequency Reference
Memory Settings ( d1-01 thru d1-09; see Table A1-4).
EXAMPLE:
o 1 - 0 4 : Digital Operator Display Units
This parameter sets the frequency units for Flux
Vector mode.
The setting of o 1 - 0 4 affects the following
parameters:
E 1 - 0 4 : Maximum Frequency
E 1 - 0 6 : Base Frequency
E 1 - 0 7 : Mid Frequency A
E 1 - 0 9 : Minimum Frequency
E 1 - 1 1 : Mid Frequency B
o 1 - 0 5 : Parameter/Address Display Selection
This parameter selects whether the parameter
addresses are displayed on the Digital Operator
by parameter number, or by its corresponding
MODBUS address number.
CAUTION
o 1 - 0 3 factory setting: 0 0 0 0 0
d 1 - 0 9 (Jog) factory setting: 0 0 6 . 00
o 1 - 0 3 changed to 1 0 6 0 0
d 1 - 0 9 setting becomes 0 0 6 0 . 0
Therefore, for 10.00 Hz Jog frequency, d 1 - 0 9 must
be reprogrammed to " 0 0 1 . 0 0 " .
5-18
Continued
o 1 - 0 3
" 1 0 0 0 0 "
=
" 2 0 0 0 0 "
=
" 3 0 0 0 0 "
=
(6 Hz)
Decimal point at X X X.X
Factory setting: 0
Range: 0 or 1
Setting
Description
0
Hertz
1
RPM
Factory setting: 0
Range: 0 or 1
Setting
Description
0
Parameter Number
1
MODBUS Address
DISPLAY
1 0 0 0 . 0
1 0 0 . 0 0
1 0 . 0 0 0