E N E R G Y SAVING OPERATION
A .
E n e r g y S a v i n g V / f C o n t r o l M e t h o d s
b 8 - 0 1 : Energy Saving Gain
This parameter is only available in the V/f or V/f w/PG Control Methods (A 1 - 0 2 = 0 or 1).
This parameter sets, in increments of 1%, the level to which the output voltage is reduced
during the energy-saving operation.
V/f
CONVERSION
Output Voltage During Energy-Saving Operation
b 8 - 0 2 : Energy Saving Frequency
This parameter is only available in the V/f or V/f w/PG control methods (A 1 - 0 2 = 0 or 1).
The energy saving function will only activate if all of the following conditions are met: a
multi-function input is activated which is set to energy savings (data 6 3), output frequency
is above the Energy Saving Frequency b 8 - 0 2, and the drive is up to its set speed (output
frequency = frequency reference).
B .
Energy Saving – Open Loop Vector &
Flux Vector Control Methods
b 8 - 0 3 : Automatic Energy Saving Selection
S e t t i n g
0
1
This parameter is only available when in the open loop vector or flux vector control methods
( A 1 - 0 2 = 2 or 3). When b 8 - 0 3 is set to a 1, a multi-function contact input is n o t required
to activate energy saving mode. This function is separate and should not be confused with
parameters b 8 - 0 1 and b 8 - 0 2. When the drive detects a lightly loaded motor, the output
voltage will automatically be reduced.
TORQUE
COMPENSATION
ENERGY-
SAVING GAIN
Disabled – Energy saving mode will not be activated under light loads.
Enabled – The energy saving mode will automatically be activated
under light loads.
Factory setting: 0
Range: 0 to 100 %
O
O
O
AND ENERGY-SAVING
Factory setting: 0 . 0
Range: 0 to 400 Hz
Factory setting: 0
Range: 0 or 1
Description
5-26
VOLTAGE COMMAND
CLOSE AT
SET FREQUENCY
ENABLED