5.26
MISCELLANEOUS PARAMETERS
o 2 - 0 2 : STOP Key Function
This parameter determines if the STOP key is operative during remote run.
Setting
o 2 - 0 5 : Digital "Motor Operated Pot"
Setting this parameter to " 1 " allows the setting of the frequency reference to imitate a
motor operated pot reference.
Setting
o 2 - 0 6 : Operator Detection Selection
Setting this parameter to " 0 " allows the drive to continue to run when the Digital
Operator is disconnected from the drive.
Setting
o 2 - 0 7 : Elapsed Timer Setting
This parameter allows the user to preset a starting value for the elapsed timer. Elapsed
time is accumulated according to the setting of o 2 - 0 8 .
0
Disabled
1
Enabled
0
Drive accepts frequency command after ENTER
is pressed
1
Drive accepts frequency reference immediately
0
Disabled (operation continues)
1
Enabled (motor coasts to stop and fault is displayed)
Continued
Factory setting: 1
Range: 0 or 1
Description
Factory setting: 0
Range: 0 or 1
Description
Factory setting: 1
Range: 0 or 1
Description
Factory setting: 0
Range: 0 or 65535
5-45