5.10
DC INJECTION BRAKING
C .
H 3 - 0 5 : Multi-function Analog Input
(Term. 16)
The multi-function analog input at terminal 16 may be configured to allow analog control of
the amount of DC injection braking current (from 0% to 100% of the current level set in
b 2 - 0 2 ), which directly controls the amount of DC injection voltage applied to the motor.
BRAKING
CURRENT
ADJUST
D .
H 1 - 0 1 thru H 1 - 0 6 : Multi-function Inputs
Any multi-function input terminal can be utilized
to control DC injection braking. When used, DC
injection current will be applied until the input is
removed, provided that the drive output
frequency is below the DC Braking Start
Frequency ( b 2 - 0 1 ) .
EXAMPLE:
H 1 - 0 6 = 60
Contact input at Terminal 8 is
the DC Injection Braking Command
RUN COMMAND
DC INJECTION
BRAKING COMMAND
OUTPUT FREQUENCY
1R
GPD 515/G5
15 +15V
16 0-10V (20K
Ω)
17
C
(Term. 3 thru 8)
DC
DC Braking Sequence
Continued
Data 6 : DC Injection Braking Current
BRAKING
CURRENT
(%)
( b2-02 )
Data 6 0 : DC Injection Braking
STOP
DC INJ. BRK. START
FREQUENCY ( b2-01 )
5-16
Adjust
100
0
ANALOG VOLTAGE
Command
GPD 515/G5
o
o
o
8 DC INJ. BRK.
COMMAND
11
0V
RAMP TO STOP
DC
10