5 . 1 4
D W E L L
b 6 - 0 1 : Dwell Frequency at Start
b 6 - 0 2 : Dwell Time at Start
b 6 - 0 3 : Dwell Frequency at Stop
b 6 - 0 4 : Dwell Time at Stop
This function allows the drive to temporarily suspend acceleration or deceleration and
remain at a desired output frequency for a specified length of time.
After receiving a run command, the drive accelerates to the designated dwell start
frequency ( b 6 - 0 1 ). The output is then held at that frequency for the duration of the
dwell time at start ( b 6 - 0 2 ). After that length of time the drive continues to accelerate
to the set frequency.
When the run command is removed the drive decelerates to the designated dwell stop
frequency ( b 6 - 0 3 ). The output is then held at that frequency for the duration of the
dwell time at stop ( b 6 - 0 4 ). After that length of time the drive continues to decelerate
until the output frequency is zero.
RUN
OUTPUT
FREQ.
b 6 - 0 1
b 6 - 0 2
5-20
Factory setting: 0 . 0
Range: 0.0 to 400.0 Hz
Factory setting: 0 . 0
Range: 0.0 to 10.0 seconds
Factory setting: 0 . 0
Range: 0.0 to 400.0 Hz
Factory setting: 0 . 0
Range: 0.0 to 10.0 seconds
SET FREQUENCY
b 6 - 0 3
b 6 - 0 4