5 . 2
A C C E L / D E C E L TIME
D .
H 3 - 0 5 : Multi-Function Analog
Input (Term. 16)
The multi-function analog input at terminal 16
may be configured to allow analog control or the
Accel/Decel time. The input voltage, in the range
of 1 to 10V, determines the coefficient by which
the Accel/Decel time is reduced:
Actual Accel/Decel Time =
EXAMPLE:
Accel/Decel Time = 10 sec *
Voltage Ref. at Term. 16 = 5V
Actual Accel/ =
Decel Time
* C1-01 or C1-02 setting, or
selected accel/decel setting.
E.
C1-10 : Accel/Decel Time Setting Unit
In addition to determining the setting resolution, this parameter controls the range of
C 1 - 0 1 thru C 1 - 0 9 ; if the resolution is 0.01 sec., the range is 0.000 to 600.00 sec. If
the resolution is set to 0.1 sec., the range is 0.0 to 6000.0 sec.
F .
C 1 - 1 1 : Accel/Decel Switching Frequency
By using C 1 - 1 1 , the Accel and Decel times can be automatically switched from Time 1
to Time 4. If the output frequency is greater than or equal to the C 1 - 1 1 frequency, the
C 1 - 0 1 and C 1 - 0 2 times are used. If the output frequency is below C 1 - 1 1 , C 1 - 0 7
and C 1 - 0 8 are used instead.
NOTE: If used in conjunction with a multi-function input ( H 1 - 0 1 thru H 1 - 0 6
set to "A" or "1A"), the multi-function input has priority over the C 1 - 1 1
switching frequency.
Continued

Accel/Decel Time

Coefficient
10 sec
= 2 sec
5 (coefficient)
5-5
Data 5 : Accel/Decel Time
Coefficient
1R
ACCEL/
DECEL
COEFFICIENT
10
5
COEFFICIENT
1
0
Factory setting: 1
Range: 0 = 0.01 seconds
1 = 0.1
Factory setting: 0 . 0
Range: 0.0 to 400.0 Hz
GPD 515/G5
15 +15V
16 0-10V (20K Ω)
17
C
1
5
10
VOLTAGE
seconds