Auto-Tuning Faults And Corrective Actions - Veikong gpd 515/g5 Startup Manual

Simplified startup procedure
Table of Contents

Advertisement

6.2
AUTO-TUNING FAULTS & CORRECTIVE ACTIONS
DIGITAL OPERATOR
DISPLAY
INDICATION
Tune Aborted
Data Invalid
Tune Aborted
Resistance
Tune Aborted
No-Load Current
Tune Aborted
Sat Coef 1
Tune Aborted
Sat Coef 2
Tune Aborted
Rated Slip
Tune Aborted
Accelerate
Tune Aborted
PG Direction
Tune Aborted
Motor Speed
Tune Aborted
Over Load
(Displayed after completion of tuning)
Tune Aborted
Minor Fault : XXX
Tune Aborted
PG Circuit
DESCRIPTION
Motor data is not correct
Line-to-line resistance not
within tolerance
No-load current (magnetizing
current) not within tolerance
Iron core saturation
coefficient 1 not within
tolerance
Iron core saturation
coefficient 2 not within
tolerance
Rated slip not within
tolerance
Motor did not accelerate in
the specified time
Encoder phasing opposite
that of motor phasing
Torque reference exceeded
100% during auto-tuning
Torque reference exceeded
20% during auto-tuning
A minor drive fault occurred
PG cable wires are
disconnected
6-6
CORRECTIVE ACTION
Check the input data.
Check the drive and motor capacities.
Check the input data.
Check the motor wiring.
Increase acceleration time ( C1-01 ).
Increase torque limit values ( L7-01 , -02 ) if they
are reduced from factory settings.
Uncouple the motor from the load.
Swap two motor leads.
OR
Swap channels on the input to the PG-X2 card
(on terminal block TA1, swap wires at terminals
4 & 6 and swap wires at terminals 5 & 7).
Uncouple motor from load.
Increase acceleration time ( C1-01 ).
Check input data, especially the encoder PPR
( F1-01 ).
Check Table 6-1 for specific minor
fault indicated by "XXX."
Pulse generator is disconnected from
the PG-X2 card (Terminal TA1).
Check PG wiring.