PROCEDURE FOR INSTALLING REPLACEMENT CONTROL PCB
1 . Record all parameters that have been changed from their factory settings, by writing
down all settings that appear under the "Modified Constants" menu.
2 . Record the Control Method ("Initialize" menu, A 1 - 0 2 ) .
3 . Record the drive's kVA selection ( o 2 - 0 4 ). This parameter is available only when
the Access Level is set to "Advanced" ( A 1 - 0 1 = 4 ) .
4 . Remove power, remove the old control board, and install the new control board.
5 . Reapply power to the drive. An " o P E 0 1
if so, step 7 will correct it.
6 . Set the Access Level to "Advanced" from the "Initialize" menu ( A 1 - 0 1 = 4 ) .
7 . Program the new control board for the correct drive size by setting parameter
o 2 - 0 4 to the value that was recorded in step 3.
8 . Set parameter o 2 - 0 9 to "American Spec" to ensure that all parameters are reset
to the "American" values when the initialization is performed in step 10.
9 . Set the new control board to the correct Control Method under the "Initialize" menu
( A 1 - 0 2 ) .
1 0 . Reset the drive from the "Initialize" menu using the "Init Parameters" function
( A 1 - 0 3 ). Entering " 2 2 2 0 " will reset the drive for 2-wire control. Entering
" 3 3 3 0 " will reset the drive for 3-wire control. NOTE: After a successful
initialization, the "Init Parameters" display will return to " No Initialize " .
1 1 . Program all parameter settings with the data that was recorded in step 1.

GPD 515/G5 SPARE PARTS

K V A S e l e c t i o n " fault may appear –