Veikong gpd 515/g5 Startup Manual page 124

Simplified startup procedure
Table of Contents

Advertisement

5 . 2 4
J O G REFERENCE
EXAMPLES:
*
RUN
COMMAND
(EXTERNAL)
JOG2
(FWD OR REV)
FREQ. CMD
d1-09 JOG
REF.
0
NOTES:
1 . Use of external Jog input is selected by setting data " 6 ", " 12 ", or " 13 "
in one of the parameters H 1 - 0 1 thru H 1 - 0 6 .
The factory configuration for 2-wire control is H 1 - 0 5 = 6,
for JOG1 input at terminal 7.
The factory configuration for 3-wire control is H 1 - 0 6 = 6,
for JOG1 input at terminal 8.
To select JOG2 - FWD, set data " 12 " into one of these parameters.
To select JOG2 - REV, set data " 13 " into one of these parameters.
JOG2 does not require an active RUN command to allow Jog operation.
2 . JOG2 (FWD or REV) has priority over FWD and REV Run in the 2-wire control
configuration, and priority over RUN, STOP, and FWD/REV commands in
3-wire control configuration.
3 . JOG2 - FWD and JOG2 - REV can be selected independently.
4 . b 1 - 0 4 = 1 (Reverse Run disabled) will override JOG2- REV.
Also see descriptions of MULTI-FUNCTION INPUT TERMINALS and RESET CODES.
Continued
JOG2 — 3-WIRE CONFIGURATION
b 1 - 0 2 = 1 (Remote Control)
*
Momentary contact.
**
When JOG2 command is released, a STOP command
is issued.
5-38
**