P H A S E LOSS DETECTION, INPUT
L 8 - 0 5 : Input Phase Loss Detection Selection
The input phase loss detection circuit monitors the DC bus current ripple and activates
when one of the input phases is lost. This causes a " PF " fault to occur and the motor to
coast to a stop.
Setting
5 . 3 5
P H A S E LOSS DETECTION, OUTPUT
L 8 - 0 7 : Output Phase Loss Detection Selection
The output phase loss detection circuit monitors the DCCT's and activates when one of the
output phases is lost. This causes a " LF " fault to occur and the motor to coast to a stop.
Setting
0
Input phase loss detection disabled
1
Input phase loss detection enabled
0
Output phase loss detection disabled
1
Output phase loss detection enabled
Description
Description
5-77
Factory setting: 0
Range: 0 or 1
Factory setting: 1
Range: 0 or 1