MULTI-FUNCTION ANALOG MONITOR OUTPUT ( T e r m . 2 1 - 2 3 )
H 4 - 0 1 : Multi-function Analog Monitor
Output 1 Selection
H 4 - 0 4 : Multi-function Analog Monitor
Output 2 Selection
The analog monitor outputs provides a 0 to ±1 0
Vdc signal between terminals 21 & 22 (or 23 &
22), proportional to the value of the U 1 - X X
parameter identified by the setting of H 4 - 0 1 ( o r
H 4 - 0 4 ). (See Appendix 1 for listing of U 1 - X X
parameters.)
Factory setting, monitor output 1 =
H 4 - 0 1 = 2 ( U 1 - 0 2 ) : Output Frequency
Factory setting, monitor output 2 =
H 4 - 0 4 = 3 ( U 1 - 0 3 ) : Drive output
This output is suitable for metering, but SHOULD NOT be used for external
control circuits. To produce an output signal for use by external control
circuits, an Analog Monitor option card (AO-08 or AO-12) must be installed
in the drive.
H 4 - 0 2 : Multi-function Analog Monitor 1 Gain
H 4 - 0 5 : Multi-function Analog Monitor 2 Gain
The settings of these parameters, in increments of 0.01, are used to calibrate the output at
terminals 21 & 22 or 23 & 22.
H 4 - 0 3 : Multi-function Analog Monitor 1 Bias
H 4 - 0 6 : Multi-function Analog Monitor 2 Bias
The settings of these parameters, in increments of 0.1 %, are used to calibrate the output
at terminals 21 & 22 or 23 & 22.
H 4 - 0 7 : Multi-function Analog Monitor Signal
Level Selection
This function allows the analog monitor output(s) to have a unipolar output signal (0-10V),
or a bipolar output signal (0 to ±1 0 V ) .
0 : Analog output is + voltage only (absolute value).
1 : Analog output is ± voltage according to sign (direction).
(10V = Fmax)
current
(5V = continuous rated current)
NOTE
5-57
Factory setting: 2
Range: 1 to 38
Factory setting: 3
Range: 1 to 38
FREQUENCY / CURRENT
GPD 515/G5
(1MA FULL SCALE)
+
Analog
21
Monitor 1
(±10 VDC
output)
G
22
Analog
Monitor 2
(±10 VDC
23
output)
Factory Setting : 1 . 0 0
Factory Setting : 0 . 5 0
Range (each): 0.00 to 2.50
Factory Setting (each): 0 . 0 %
Range (each): –10.0 to +10.0 %
Factory Setting: 0
Range: 0 or 1
METER
MULTI-
FUNCTION
MONITOR
OUTPUT 1
G
MULTI-
FUNCTION
+
MONITOR
OUTPUT 2