TROUBLESHOOTING CHART 6.1 (Continued)
VOLTAGE PRESENT ACROSS
OUTPUT TERMINALS
T1(U), T2(V) AND T3(W)?
PROPER CONNECTIONS
NO
CONTROL METHOD?
V/F w/ PG
Flux Vector
PROPER
CONNECTIONS
FROM DRIVE
TO PG
(ENCODER)?
NO
YES
VOLTAGE PRESENT AT
MOTOR TERMINALS
T1(U), T2(V) AND T3(W)?
VOLTAGE BALANCED
BETWEEN PHASES, AT
T1(U), T2(V) AND T3(W)?
FROM
A
PRECEDING
PAGE
YES
FROM DRIVE TO
MOTOR?
YES
V/F
Open Loop Vector
TORQUE LIMIT
SETTING
CORRECT?
YES
YES
YES
LOAD TORQUE
TOO LARGE?
NO
(WITHIN 2%)
YES
MOTOR
IS FAULTY.
6-12
NO
DRIVE
IS FAULTY.
SET TORQUE LIMIT
(ANALOG INPUT, OR
NO
L7-01 & L7-02 ) TO
PROPER VALUE.
CHECK FOR
PROBLEM IN MOTOR,
NO
MECHANICAL
SYSTEM OR BRAKE.
- REDUCE LOAD
TORQUE (DISCON-
NECT LOAD).
- REPLACE DRIVE
WITH ONE OF
LARGER CAPACITY.
NO
DRIVE
IS FAULTY.