1.4

ELECTRICAL INSTALLATION

All basic interconnections (using the Digital Operator) are shown in Figures 1-3 and 1-4.
1 . 4 . 1
M a i n C i r c u i t I n p u t / O u t p u t
Complete wire interconnections according to Table 1-2, Figure 1-3 and Figure 1-4. Be sure to
observe the following:
• Use 600V vinyl-sheathed wire or equivalent. Wire size and type should be determined by local
electrical codes.
• Avoid routing power wiring near equipment sensitive to electrical noise.
• Avoid running input and output wiring in the same conduit.
• NEVER connect AC main power to output terminals T1(U), T2(V), and T3(W).
• NEVER allow wire leads to contact metal surfaces. Short-circuit may result.
• NEVER connect power factor correction capacitors to the drive output. Consult
Yaskawa when connecting noise filters to the drive output.
• WIRE SIZING MUST BE SUITABLE FOR CLASS I CIRCUITS.
• When connecting motor to drive's output terminals, include a separate ground wire. Attach ground
wire solidly to motor frame and to drive's ground terminal.
• When using armored or shielded cable for connection between drive and motor, solidly connect
armor or shield to motor frame, and to drive's ground terminal.
• Motor lead length should NOT EXCEED 164 feet (50 meters), and motor wiring should be run in
a separate conduit from other power wiring. If lead length must exceed this distance, reduce
carrier frequency (see paragraph 5.8) and consult factory for proper installation procedures.
• Use UL listed closed loop connectors or CSA certified ring connectors sized for the selected wire
gauge. Install connectors using the correct crimp tool recommended by the connector
manufacturer.
WIRE SIZE
AWG
mm
20
0.5
18
0.75
16
1.25
14
2
12
3.5
10
5.5
8
8
6
14
4
22
2
38
1/0
60
3/0
80
4/0
100
MCM300
150
MCM400
200
MCM650
325
TERMINAL
SCREW
2
M3.5
M4
M4
M4
M5
M4
M5
M4
M5
M5
M6
M6
M8
M8
M10
M10
M10
M10
M12
M12
M12
M12
M16
CLOSED-LOOP
CONNECTOR
lb-in
1.25 - 3.5
7.8
1.25 - 4
13.0
1.25 - 4
13.0
2 - 4
13.0
2 - 5
26.1
3.5 - 4
13.0
3.5 - 5
26.1
5.5 - 4
13.0
5.5 - 5
26.1
8 - 5
26.1
8 - 6
40.9
14 - 6
40.9
22 - 8
100.0
38 - 8
100.0
38 - 10
182.6
60 - 10
182.6
80 - 10
182.6
100 - 10
182.6
100 - 12
313.0
150 - 12
313.0
200 - 12
313.0
325 - 12
313.0
325 - 16
313.0
1-2
CLAMPING TORQUE
STEEL
COPPER
N-m
lb-in
0.9
7.0
1.5
10.4
1.5
10.4
1.5
10.4
20.9
3.1
1.5
10.4
20.9
3.1
1.5
10.4
20.9
3.1
20.9
3.1
34.8
4.8
34.8
4.8
82.6
11.7
82.6
11.7
156.5
21.4
156.5
21.4
156.5
21.4
156.5
21.4
191.3
36.7
191.3
36.7
191.3
36.7
191.3
36.7
191.3
36.7
N-m
0.8
1.2
1.2
1.2
2.4
1.2
2.4
1.2
2.4
2.4
4.1
4.1
10.7
10.7
18.4
18.4
18.4
18.4
23.1
23.1
23.1
23.1
23.1