5 . 3 7
R E S E T CODES: 2-WIRE, 3-WIRE INITIALIZATION
A 1 - 0 3 : Parameter Selection /
Initialization
By entering either " 2220 " or " 3330 " into this parameter, a reset to factory
configuration (parameter initialization) is accomplished. The parameters which are NOT
affected are:
A 1 - 0 0 : Language Selection
A 1 - 0 2 : Control Method
Parameter Terminal
H 1 - 0 1
3
H 1 - 0 2
4
H 1 - 0 3
5
H 1 - 0 4
6
H 1 - 0 5
7
H 1 - 0 6
8
Know your application before using either Initialization function of A1-03 . This
parameter must be set to " 0 " for Drive mode operation.
" 1110 " = User Default Parameter Initialization
" 2220 " = Factory 2-Wire Control Initialization (Maintained RUN Contact)
" 3330 " = Factory 3-Wire Control Initialization (Momentary START/STOP
Entering either Initialization code resets all parameters to factory settings (except
for A1-00, A1-02, o2-04, & E1-03), and automatically returns A1-03 setting to " 0 "
(No Initialization). If the GPD 515 is connected for 3-Wire control and this parameter
is set to " 2220 " (2-Wire Control Initialization), the motor may run in reverse
direction WITHOUT A RUN COMMAND APPLIED. Equipment damage or personal
injury may result.
When o 2 - 0 3 = 1, the existing parameter settings become default user settings and the
" 1110 " initialization option appears in A 1 - 0 3 . When o 2 - 0 3 is not set to " 1 ", this
option is not available. Anytime the A 1 - 0 3 parameter is set to " 1110 ", all parameter
settings that have been changed return to the default user settings (only 50 parameters
may be stored as default settings). This is NOT a Factory Initialization.
Selection
2 - W i r e C o n t r o l
" 24 " = External Fault
" 14 " = Fault Reset
" 3 " = Multi-step Ref. Select 1
" 4 " = Multi-step Ref. Select 2
" 6 " = Jog Freq. Ref.
" 8 " = External Base Block
Contact)
Factory setting: 0
Data:
0
= No Initialization
1 1 1 0 = User Default Parameter
2 2 2 0 = 2-Wire Control Initialization
3 3 3 0 = 3-Wire Control Initialization
E 1 - 0 3 : V/f Pattern Selection
o 2 - 0 4 : GPD 515 Capacity
Factory Configuration for
" 24 " = External Fault
" 14 " = Fault Reset
CAUTION
5-83
Initialization
3 - W i r e C o n t r o l
" 0 " = FWD/REV Command
" 3 " = Multi-step Ref. Select 1
" 4 " = Multi-step Ref. Select 2
" 6 " = Jog Freq. Ref.
(N.O. contact)