5.15
ENCODER (PG) PARAMETERS
D .
F 1 - 1 0 : Excessive Speed Deviation
Detection Level
F 1 - 1 1 : Excessive Speed Deviation
Detection Delay Time
F 1 - 0 4 : Operation Selection at
Speed Deviation
Parameters F 1 - 1 0 and F 1 - 1 1 work together to determine when a Speed Deviation
( D E V ) fault will occur. Parameter F 1 - 1 0 determines how far the motor speed has to
differ from the speed reference (set as a percentage of E 1 - 0 4 ), and F 1 - 1 1 determines
how long the speed has to deviate before a fault will occur. Use F 1 - 0 4 to determine
stopping method if a speed deviation fault occurs.
EXAMPLE:
F 1 - 1 0 = 1 0 %, F 1 - 1 1 = 0 . 5 sec, F 1 - 0 4 = 1 , and E 1 - 0 4 (Max
Frequency) = 6 0 Hz. As can be seen below, the motor speed must drop
over 10% below the speed reference for 0.5 seconds before a fault occurs.
10% speed = E 1 - 0 4 x 0.1 = 60 x 0.1 = 6Hz
Only available in the V/f w/PG and Flux Vector Control Methods
( A 1 - 0 2 = 1 or 3).
Continued
Factory setting: 1 0
Range: 0 to 50 %
Factory setting: 0 . 5
Range: 0.0 to 10.0 seconds
Factory setting: 3
Range: 0 : Ramp to Stop
NOTE
5-23
1 : Coast to Stop
2 : Fast-stop
3 : Alarm Only