Momentary Power Loss Ride-Thru - Veikong gpd 515/g5 Startup Manual

Simplified startup procedure
Table of Contents

Advertisement

5.28
MODBUS CONTROL
H 5 - 0 4 : Stopping Method After Serial
Communication Error ( CE )
Setting
5 . 2 9
M O M E N T A R Y POWER LOSS RIDE-THRU
L 2 - 0 1 : Momentary Power Loss Ride-thru
Protection
The setting of this parameter either enables or disables the ride-thru feature of the
drive. If disabled, the unit will stop immediately whenever a power loss occurs. If enabled,
the drive will continue to operate during a momentary power loss of up to 80%, but if the
loss exceeds the identified time period, the drive will stop.
L 2 - 0 2 : Power Loss Ride-Thru
Deactivation Time
If the loss exceeds the length of time identified by L 2 - 0 2 , the drive will stop. The
factory setting of this parameter, in 0.1 second increments, is related to the drive's
capacity rating (see Appendix 3).
Note that the RUN command must be maintained throughout the ride-thru period. If
L 2 - 0 1 is set to " 2 ", a " U V " alarm is displayed during power loss, and no fault signal is
output at any multi-function output that is programmed for a fault.
Continued
0
Ramp to Stop (using C1-02 )
1
Coast to Stop (base block)
2
Fast-stop (using C1-09 )
3
Alarm Only (operation continues)
Description
0 = Disabled (Factory setting)
1 = Enabled – 2 sec. power loss
ride-thru
2 = Enabled – indefinite power loss
ride-thru, provided control
power is maintained
Factory setting: See Table A3-1
Range: 0.0 to 2.0 seconds
5-50
Factory setting: 3
Range: 0 to 3