5.15

ENCODER (PG) PARAMETERS

A .
F 1 - 0 1 : Encoder (PG) Constant
This parameter is set to the Pulses Per Revolution (ppr) to the encoder used with the motor.
B .
F 1 - 0 2 : Operation Selection at PG
Open Circuit
F 1 - 1 4 : PG Open Circuit Detection
Delay Time
The setting of F 1 - 0 2 determines the stopping method when a PG Open Circuit ( PGo ) is
detected. A PG open circuit is detected when no pulses are received from the pulse
generator within the time specified by F 1 - 1 4 . (Note: The PG Open fault is disabled when
zero speed is commanded.)
Only available in the V/f w/PG and the Flux Vector Control Methods
( A 1 - 0 2 = 1 or 3).
Factory setting: 1 0 2 4
Range: 0 to 60000 ppr
Factory setting: 1
Range: 0 : Ramp to Stop
Factory setting: 2 . 0
Range: 0.0 to 10.0 seconds
NOTE
5-21
1 : Coast to Stop
2 : Fast-stop
3 : Alarm Only