5.28
MODBUS CONTROL
H 5 - 0 1 : Serial Communication Station Address
Each slave on the same transmission line must be given a unique address.
H 5 - 0 2 : Serial Communication Baud Rate
Selects the baud rate, as indicated by the following table:
Setting
H 5 - 0 3 : Serial Communication Parity Selection
Selects the parity, as indicated by the following table:
Setting
NOTE: To change the values set in H 5 - 0 1 thru H 5 - 0 3 and enable
the new settings, it is necessary to turn OFF power to the Drive, then
turn it ON again.
H 5 - 0 5 : Serial Communication Error ( CE )
Detection
This parameter determines whether or not the drive will detect a CE condition. The
corresponding action the drive will take is dependent upon the setting of H 5 - 0 4 .
Setting
Continued
Baud Rate (BPS)
0
1
2
3
4
0
1
2
Description
0
Disabled
1
Enabled
1200
2400
4800
9600
19.2 K
Parity
None
Even
Odd
5-49
Factory setting: 1 F
Range: 1 to 1F (Hex)
(= 1 to 31 decimal)
Factory setting: 3
Range: 0 to 4
Factory setting: 0
Range: 0 to 2
Factory setting: 1
Range: 0 or 1