Frequency Reference Input Signals (Auto/Manual) - Veikong gpd 515/g5 Startup Manual

Simplified startup procedure
Table of Contents

Advertisement

5.19

FREQUENCY REFERENCE INPUT SIGNALS (AUTO/MANUAL)

H 3 - 0 1 : Auto Speed Reference Signal
Level Selection (Term. 13)
To change the control circuit terminal 13 input level, program H 3 - 0 1 .
Setting
H 3 - 0 4 : Multi-function Analog Input 1 Signal
Level Selection (Term. 16)
To change the control circuit terminal 16 input level, program H 3 - 0 4 .
Setting
H 3 - 0 8 : Multi-function Analog Input 2 Signal
Level Selection (Term. 14)
To change the control circuit terminal 14 input level, program H 3 - 0 8 .
Setting
In addition to setting parameter H 3 - 0 8 = 0 or 1 for a voltage input,
jumper J1 on the drive's Control PCB must be cut.
Examples of wiring the drive for frequency references from various sources are shown on
the next page.
If parameter H 3 - 0 9 = 1F terminals 13 and 14 are added and used as the internal
frequency reference.
Terminal 13 Input Level
0
1
Terminal 16 Input Level
0
1
Terminal 14 Input Level
0
1
2
IMPORTANT
0 to 10 V
–10 to 10 V
0 to 10 V
–10 to 10 V
0 to 10 V
–10 to 10 V
4 to 20 mA
NOTE
5-31
Factory setting: 0
Range: 0 or 1
Factory setting: 0
Range: 0 or 1
Factory setting: 2
Range: 0 to 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents