Veikong gpd 515/g5 Startup Manual page 145

Simplified startup procedure
Table of Contents

Advertisement

5 . 3 2
M U L T I - F U N C T I O N INPUT TERMINALS ( T e r m . 3 - 8 )
T a b l e 5 - 2 . H 1 - 0 1 t h r u H 1 - 0 6 D a t a S e t t i n g s
DATA
FUNCTION
DATA
FUNCTION
0
Forward/Reverse selection
f o r 3 - w i r e c o n t r o l
1
Local/Remote selection
2
Option / drive reference
selection
3
Multi-step reference
select 1
4
Multi-step reference
select 2
5
Multi-step reference
select 3
6
Jog frequency reference
7
Accel/decel time
selection 1
8
External base block
(N.O. contact input)
9
External base block
(N.C. contact input)
A
Accel/decel ramp hold
(speed hold command)
B
External overheat alarm
signal
C
Multi-function analog input
selection
D
Speed control disable
E
ASR integral reset (IRST)
F
Terminal Not Used
DESCRIPTION
Signal Levels: 0 = state; 1 = pulse
DESCRIPTION
Redefines terminals to:
1 = Run; 2 = Stop; corresponding
terminal (3-8) = FWD/REV select
Open = Operates according to setting of
b 1 - 0 1 and b 1 - 0 2
Closed = Operates from keys of the Digital
Operator
S e e D a t a d e s c r i p t i o n f o l l o w i n g t h i s t a b l e
Open = Operates from Digital Operator and or
external terminals
Closed = Operates from installed option
S e e p a r a g r a p h 5 . 2 5 B
Closed = Jog selected
S e e p a r a g r a p h 5 . 2 4 & 5 . 2 5 B
Open = Accel/decel by C 1 - 0 1 / C 1 - 0 2
Closed = Accel/decel by C 1 - 0 3 / C 1 - 0 4
S e e p a r a g r a p h 5 . 2 B
Closed = Shuts off drive output
(speed reference is held)
S e e D a t a d e s c r i p t i o n f o l l o w i n g t h i s t a b l e
Open = Shuts off drive output
(speed reference is held)
S e e D a t a d e s c r i p t i o n f o l l o w i n g t h i s t a b l e
Closed = Hold
S e e p a r a g r a p h 5 . 2 B
Closed = " oH2 " blinks on the Digital Operator,
and operation continues (minor fault)
Open = Analog inputs (terms. 14 & 16) are
disabled
Closed = Analog inputs (terms. 14 & 16) are
enabled
Open = Speed control enabled
Closed = Speed control disabled
Closed = Integral reset
S e e p a r a g r a p h 5 . 7 C
Drive does not react to input
5-59
Continued
AVAILABILITY
(See Note 1)
0
1
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2
3
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

Hide quick links:

Advertisement

Table of Contents
loading