Veikong gpd 515/g5 Startup Manual page 48

Simplified startup procedure
Table of Contents

Advertisement

2 . 2 a
( c o n t i n u e d )
DESCRIPTION
Check the motor rotation using
the JOG function.
NOTE: The frequency
reference for this
operation comes
from d1-09 and is
factory set to 6 Hz.
WARNING
THE NEXT KEY-PRESS
WILL CAUSE THE MOTOR
TO MOVE; TAKE APPRO-
PRIATE PRECAUTIONS.
The motor should ramp up to
speed, and rotation should be
counter-clockwise if the FWD
light is on. Rotation should be
clockwise if the REV light is on.
If rotation is incorrect, reverse
any two motor leads, then
repeat the motor rotation check.
Run the Auto-Tuning routine:
WARNING
THE MOTOR WILL MOVE
WHEN AUTO-TUNING IS
EXECUTED! TAKE
PROPER PRECAUTIONS!
CAUTION
Motor should be discon-
nected from the load before
executing the auto-tuning
routine.
NOTE: If the motor cannot be
disconnected from the
load, or if Auto-Tuning
fails, motor parameters
should be entered
manually. See section
2.4 for the procedure.
Enter the motor nameplate
values needed to perform Auto-
tuning
KEY SEQUENCE
Press
, then
MENU
If either or both of the SEQ and REF lights are
on, press
LOCAL
REMOTE
Press & hold
JOG
Release
JOG
Press
, then
MENU
2-4
DATA
ENTER
RUN light will illuminate
3 times
DIGITAL OPERATOR
Frequency Ref
U1-01= 0.00 HZ
Frequency Ref
U1-01= 6.00 HZ
** Main Menu **