T a b l e A 2 - 1 . S t a n d a r d S p e c i f i c a t i o n s ( C o n t i n u e d )
Stall Prevention
Protective
Functions
(continued)
Ground Fault
Power Charge Indication
Location
Ambient Temperature
Environmental
Conditions
Storage Temperature (Note 3)
Humidity
Vibration
Elevation
Rated speed
Pulse Generator
Thermistor
Load Connection
Insulation Type
Ambient Temperature
Location
NOTES:
1 .
Overload capacity: 150% of rated for 60 sec.
2 .
See paragraph 5.29 for detailed information.
3 .
Temperature during shipping. Storing in this temperature for a long period may deteriorate main circuit capacitor.
4 .
1HP motor VMB001C is an inverter-duty foot mount with C-Face.
SECTION C. ALL drives (Continued)
SECTION C. ALL drives (CONTINUED)
Stall prevention at acceleration /deceleration and constant
speed operation.
Provided by electronic circuit.
"CHARGE" lamp remains lit until bus voltage drops below 50 V.
Indoor (protected from corrosive gases and dust)
–10 to 40°C (+14 to 104°F) for NEMA 1;
–10 to 45°C (+14 to 113°F) for protected chassis
–20 to 60°C (–4 to 140°F)
95% RH (no condensation)
1 G at less than 20 Hz, up to 0.2 G at 20 to 50 Hz
3300 ft (1000 m) or less
SECTION D. All VCMs
SECTION D
1750 rpm (4 poles, 60Hz)
1024 ppr
Standard
Direct coupling or belt drive
Class F
–20 to +40°C (–4 to +104°F)
Indoor
A2-4