Veikong gpd 515/g5 Startup Manual page 89

Simplified startup procedure
Table of Contents

Advertisement

5 . 2
A C C E L / D E C E L TIME
A .
C 1 - 0 1 : Accel Time 1
C 1 - 0 2 : Decel Time 1
C 1 - 0 3 : Accel Time 2
C 1 - 0 4 : Decel Time 2
C 1 - 0 5 : Accel Time 3
The drive incorporates four sets of individually programmable acceleration and deceleration
times.
B .
H 1 - 0 1
t h r u
function Inputs (Term. 3 thru 8)
By programming data " 7 " into one of the
multi-function parameters ( H 1 - 0 1 thru
H 1 - 0 6 ), the corresponding multi-function input
terminal (3 thru 8) becomes the Time Selection 1
input. When the input terminal (i.e. external
contact) is open, Time 1 ( C 1 - 0 1 / C 1 - 0 2 ) is
selected. When the input terminal is closed,
Time 2 ( C 1 - 0 3 / C 1 - 0 4 ) is selected. By
programming data " 1A " into another of the
multi-function parameters, the corresponding
multi-function input terminal becomes the Time
Selection 2 input. When the input terminal is
open, Time 1 or 2 is selected based on the setting of the Time Selection 1 input. When
the input is closed, Time 3 ( C 1 - 0 5 / C 1 - 0 6 ) or Time 4 ( C 1 - 0 7 / C 1 - 0 8 ) is selected
based on the status of the Time Selection 1 input.
Accel/Decel
Selection 2
H1-06 = 1A
Open
Open
Closed
Closed
C 1 - 0 6 : Decel Time 3
C 1 - 0 7 : Accel Time 4
C 1 - 0 8 : Decel Time 4
C 1 - 0 9 : Fast Stop
H 1 - 0 6 : Multi-
Accel/Decel
Selection 1
H1-05 = 07
Open
Closed
Open
Closed
Factory setting (each): 1 0 . 0
Range* (each): 0.0 to 6000.0
(* Note: see para. 5.2 E)
Decel Time
Data 7 : Accel/Decel Time Selection 1
Data 1 A : Accel/Decel Time Selection 2
TIME SELECTION 1
o
TIME SELECTION 2
o
Accel Time
C1-01
C1-03
C1-05
C1-07
5-3
seconds
GPD 515/G5
o
o
7
o
o
8
11
0V
Decel Time
C1-02
C1-04
C1-06
C1-08

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents