Section 2.
2.1

PRE-POWER CHECKS

• Verify wires are properly connected and no erroneous grounds exist.
• Remove all debris from the drive enclosure. Check for loose wire clippings.
• Verify all mechanical connections inside the drive are tight.
• Verify motor is not connected to load.
• Apply input power only after the front cover is in place. DO NOT remove the front
cover or Digital Operator while input power is on.
F o r 4 6 0 V , G P D 5 1 5 C - B 0 4 1 t h r u - B 0 9 6 ( C I M R - G 5 M 4 0 P 4 1 F t h r u 4 0 4 5 1 F ):
Verify that the drive power voltage select connector, located at lower left corner inside
drive chassis (see Figure 2-1), is positioned correctly for the input power line voltage.
Voltage is preset to 460V at the factory. Reposition, if required, to match nominal line
voltage.
23CN 24CN 25CN 26CN 22CN
20CN
TB1
F i g u r e 2 - 1 a . P o w e r V o l t a g e S e l e c t i o n i n 4 6 0 V d r i v e
F i g u r e 2 - 1 b .
P o w e r V o l t a g e S e l e c t i o n
i n 6 0 0 V D r i v e

INITIAL START-UP ("LOCAL" CONTROL)

s
r
+
+
380V 400/415V 440V
FU2
21CN
460V
For 600V, GPD515C-C027 thru -C200
( C I M R - G 5 M 5 0 1 8 1 F t h r u 5 1 6 0 0 F ).
Verify that the drive power voltage select
connector, located at lower left corner
inside drive chassis (see Figure 2-1b), is
positioned correctly for the input power line
voltage. Voltage is preset to 600V at the
factory. Reposition, if required, to match
nominal line voltage.
2-1
• •