Veikong gpd 515/g5 Startup Manual page 185

Simplified startup procedure
Table of Contents

Advertisement

5 . 4 4
T O R Q U E DETECTION
D .
H 3 - 0 5 : Multi-function Analog Input
(Term. 16)
The multi-function analog input at terminal 16 may be configured to allow analog control
of the overtorque detection level. When this function is programmed into H 3 - 0 5 , the
internal overtorque detection level ( L 6 - 0 2 ) is disabled.
E .
H 2 - 0 1 : Multi-function Output (Term. 9 & 10)
H 2 - 0 2 : Multi-function Output (Term. 25-27)
H 2 - 0 3 : Multi-function Output (Term. 26-27)
A contact, or two open collector outputs, can be programmed to change states during an
overtorque detection condition.
Continued
OVERTORQUE
DETECTION
LEVEL
200%
OVERTORQUE
DETECTION
LEVEL
0%
Data 7 : External Overtorque
1R
drive/G5
15 +15V
16 0-10V (20 KΩ)
17
C
0V
VOLTAGE REFERENCE
5-99
Detection Level Adjustment
10V
Data B : Overtorque
Detection