Veikong gpd 515/g5 Startup Manual page 153

Simplified startup procedure
Table of Contents

Advertisement

5 . 3 2
M U L T I - F U N C T I O N INPUT TERMINALS ( T e r m . 3 - 8 )
SAMPLE/
HOLD CMD Open
G .
Data 1 0 : Up Function
Data 1 1 : Down Function
d 4 - 0 1 : Frequency Reference Hold
Function Selection
Programming data " 10 " and " 11 " for two of the six multi-function input terminals allows
those inputs to be used for Up/Down frequency setting by simulating the action of a MOP
(motor operated potentiometer).
NOTES:
1. Set parameter b 1 - 0 2 = 1.
2. OPE3 fault will occur if " 10 " and " 11 " data settings are not used together.
3. OPE3 fault will occur if " 10 " and " 11 " data settings are programmed at the
same time as setting " A " (Accel/decel ramp hold).
4. Jog has priority over Up/Down function.
5. Up/Down has priority over Multi-step Speed inputs.
6. Up/Down is ineffective when operation is from the Digital Operator.
(NOTES continued on next page)
10V
8V
ANALOG INPUT
5V
0.1
sec.
Closed
t1
0.11
sec.
Sample/Hold Function Timing
0.1
sec.
t2
t3
0.05
0.15
sec.
sec.
Factory setting: 0
Data: 0 = Disabled
5-67
Continued
100%
80%
FREQ. REF.
50%
1 = Enabled