P I D C O N T R O L
E .
Feedback Loss Detection
b 5 - 1 2 : Feedback Loss Detection Selection
Setting
0
1
2
b 5 - 1 3 : Feedback Loss Detection Level (PID)
b 5 - 1 4 : Feedback Loss Detection
Delay Time (PID)
When feedback loss detection is enabled (b 5 - 1 2 = data "1" or "2"), the drive will detect if
the feedback signal falls below the b 5 - 1 3 level for more than the b 5 - 1 4 delay time and
respond according to the setting of b 5 - 1 2.
F .
Multi-Function Input Terminals
H 1 - 0 1 t h r u H 1 - 0 6 : Multi-function Inputs
By programming data "30" into one of the multi-function parameters (H 1 - 0 1 thru H 1 -
0 6), the corresponding multi-function input terminal (3 thru 8) will reset the integrator's
value to zero.
H 1 - 0 1 t h r u H 1 - 0 6 : Multi-function Inputs
By programming data "31" into one of the multi-function parameters (H 1 - 0 1 thru H 1 -
0 6), the corresponding multi-function input terminal (3 thru 8) will hold the integrator's
output value. When the contact is closed (on the Multi-Function Input Terminal), whatever
value the integrator is outputting will remain the same until the contact is opened.
Continued
Feedback loss detection is disabled
Feedback loss detection is enabled - alarm only
(drive continues running).
Feedback loss detection is enabled - fault (drive coasts to stop)
(Term. 3 thru 8)
(Term. 3 thru 8)
Factory setting: 0
Range: 0 to 2
Description
Factory setting: 0
Range: 0 to 100 %
Factory setting: 1 . 0
Range: 0.0 to 25.5
Data 3 0 : PID Integral Reset
Data 3 1 : PID Integral Hold
5-82