5 . 3 2
M U L T I - F U N C T I O N INPUT TERMINALS ( T e r m . 3 - 8 )
A .
Data 1 : Local/Remote
Set b 1 - 0 1 and b 1 - 0 2 to data " 1 " to select external inputs as the source for
frequency reference and operation commands. The use of a Local/Remote command input
allows switching between Digital Operator control and the external terminal input signals,
without the need to re-program b 1 - 0 1 and b 1 - 0 2 . If the status of the Local/Remote
command input is changed while the drive is running, the Local/Remote operation selection
is not completed until the next time the drive is stopped.
Closed = Controlled locally (Digital Operator)
Open = Controlled according to the setting of b 1 - 0 1 and b 1 - 0 2
If manual speed is selected
– by the external Auto/Manual switch (3SS [2-wire] or 2SS [3-wire]),
– by jumper from terminal 5 to 11 (2-wire control),
o r – by jumper from terminal 6 to 11 (3-wire control),
the drive speed reference will be controlled by manual speed reference
regardless of the state of the Local/Remote input.
b 1 - 0 7 : Local / Remote Run Selection
When switching from local (digital operator) back into remote (terminals) and a remote
run command is present, parameter b 1 - 0 7 determines how the drive will react. With a
setting of "1", the drive will start running as soon as remote mode is selected. A setting
of " 0 " will require the run command to be removed and re-applied after the remote
mode is selected.
S e t t i n g
0
Cycle External Run
1
Accept External Run
NOTE
Description
5-62
Continued
Factory Setting: 0
Range: 0 to 1