5.30
MULTI-FUNCTION ANALOG INPUTS ( T e r m . 1 4 & 1 6 )
DATA
FUNCTION
DATA
13
Torque reference (in
Torque Control);
Torque limit (in Speed
Control)
14
Torque compensation
15
Torque limit
1F
"Not Used"
NOTES:
1 .
For a bidirectional pot input instead of 0-10V, set H 3 - 0 4 = 1 (for terminal 16) or
H 3 - 0 8 = 1 (for terminal 14), and connect the low (negative) side of the pot to
terminal 33. If using a –10 to +10V input, connect the positive side to terminal 16
or 14, and the negative side to terminal 17.
2 .
Column headings refer to set value of A 1 - 0 2 , Control Method; 0 = V/f,
1 = V/f w/PG, 2 = Open Loop Vector, 3 = Flux Vector. "X" in column indicates
Available, "—" indicates Not Available.
3 .
Quadrant 1 is forward motor rotation, torque in forward direction;
Quadrant 2 is forward motor rotation, torque in reverse direction (regeneration);
Quadrant 3 is reverse motor rotation, torque in reverse direction;
Quadrant 4 is reverse motor rotation, torque in forward direction (regeneration).
H3-05 = 0
H3-09 = 0
FREQUENCY
REF.
–10V
MULTI-FUNCTION ANALOG INPUT
FUNCTION
10V = 100% of motor rated torque (forward & reverse)
Quadrants 1, 2, 3, & 4 (See Note 3)
See paragraph 5.43.
When programmed in H3-05, terminal 16 input has no effect.
When programmed in H3-09, terminal 14 input is added to
the terminal 13 frequency reference.
100%
0%
0V
10V
–100%
DESCRIPTION
REMARKS
H3-05 = 1
H3-09 = 1
FGAIN
–10V
MULTI-FUNCTION ANALOG INPUT
5-54
Continued
AVAILABILITY
AVAILABILITY
(See Note 2)
(SEE NO
0,1
2
0, 1
2
X
X
X
100%
0%
0V
10V
–100%
3
3
X
X
X
X