Veikong gpd 515/g5 Startup Manual page 258

Simplified startup procedure
Table of Contents

Advertisement

T a b l e A 1 - 8 . D r i v e L X - X X P a r a m e t e r s – C o n t i n u e d
PARAMETER
F U N C T I O N
NUMBER
N A M E
L8-03
Operation
Selection After
OH (Overheat)
Pre-alarm
L8-05
Input
Open-phase
Protection
Selection
L8-07
Output
Open-phase
Protection
Selection
L8-10
Output Ground
Fault Detection
Selection
L8-17
IGBT
Protection
at Low
Frequency
L8-19
OL2 Selection
at Low Speed
NOTES:
1 .
Factory setting differs depending on drive capacity.
2 .
When Vector control ( A 1 - 0 2 = 2 or 3) is selected, set value 2 (Intelligent) cannot
be set.
3 .
Factory setting differs depending on the Control Method selected by ( A 1 - 0 2 ) .
4 .
Capability to view and set specific parameters is dependent upon the Access Level
( A 1 - 0 1 ) and Control Method ( A 1 - 0 2 ; 0 = V/f, 1 = V/f w/PG, 2 = Open Loop
Vector, 3 = Flux Vector) the drive is programmed for. Each column represents the
Access Level for a given Control Method: Q = Quick-start; B = Basic; A = Advanced;
— = not available.
D E S C R I P T I O N
0 : Ramp to stop
1 : Coast to stop
2 : Fast-stop
3 : Alarm only
0 : Disabled
1 : Enabled
0 : Disabled
1 : Enabled
0 : Disabled
1 : Enabled
0 : Conventional
1 : Lower carrier frequency
when I > 100% and
Fout < 10.0 Hz
2 : Short Term OL2
(2 seconds if Fout
< 6.0 Hz and I > 175%
3 : Limit current to 150%
0 : Low frequency OL2
disabled
1 : Low frequency OL2
enabled
INCRE-
S E T T I N G
M E N T
RANGE
1
0 - 3
1
0, 1
1
0, 1
1
0, 1
1
0 - 3
1
0, 1
A1-24
A C C E S S L E V E L
F A C T O R Y
( S e e N o t e 4 )
S E T T I N G
0
1
2
3
A A
A A
0
A A
A A
1
A A
A A
1
A A
A A
1
A A
A —
0
A A
A A
P A R A .
REF .
3
5.27
5.34
5.35
5.27
5.27
5.27