5.33
MULTI-FUNCTION OUTPUT T E R M I N A L S ( T e r m . 9 & 1 0 ; 2 5 - 2 7 )
H 2 - 0 1 : Contact Output (external
terminals 9 & 10)
H 2 - 0 2 : Open Collector Output
(external terminals 25 & 27)
H 2 - 0 3 : Open Collector Output
(external terminals 26 & 27)
A contact, or two different open collector
outputs, can be programmed to change states
during any of the conditions indicated in Table
5-3.
If an open collector output is applied to a DC relay, the relay MUST be diode
protected, as shown in the recommended configuration below.
Recommended
Configuration for
DC Relays
GPD 515/G5
IMPORTANT
25
DIODE
26
27
C
5-70
MULTI-FUNCTION
CONTACT OUTPUT
250Vac 1A OR LESS
o o
9
30Vdc 1A OR LESS
(FACTORY SETTING
10
IS FOR SIGNAL
DURING OPERATION)
25
MULTI-
FUNCTION
OPEN
COLLECTOR
26
OUTPUTS
48Vdc AT
50mA MAX.
27
48Vdc MAX. *
*
DC
L
*
RELAY
* Customer
supplied