Stopping Method - Veikong gpd 515/g5 Startup Manual

Simplified startup procedure
Table of Contents

Advertisement

5 . 4 0
S T O P P I N G METHOD
b 1 - 0 3 : Stopping Method Selection
Selects the stopping method suitable for the application.
S e t t i n g
A .
Data 0 : Deceleration to Stop
Upon removal of the FWD (REV) Run
command, the motor decelerates at
the deceleration rate determined by
the time set in Decel Time 1
( C 1 - 0 2 ), and DC injection braking
is applied immediately before stop.
If the decel time is too short or the
load inertia is too large, an
overvoltage ( O V ) fault may occur
on a stop command — the decel
time must be increased.
B .
Data 1 : Coast to Stop
Upon removal of the FWD (REV) Run command, the motor coasts to rest.
Output Frequency
Run Command
0
Deceleration (ramp) to stop
1
Coast to stop
2
Full range DC injection to stop
3
Coast to stop with timer
Output Frequency
Min. Output Frequency
(Frequency at DC Injection
Braking Start) ( b2-01 )
(Factory setting: 0.5 Hz)
ON
D e s c r i p t i o n
ON
Run Command
Drive output is shut OFF
when stop command is input
OFF
5-88
Factory setting: 0
Range: 0 to 3
Decel Time 1
( C1-02 )
DC Injection Braking
Time at Stop ( b2-04 )
(Factory setting: 0.5 s)
OFF