5.26
MISCELLANEOUS PARAMETERS
o 2 - 0 8 : Elapsed Timer Selection
This parameter determines whether the timer is active whenever power is applied to the
drive or whenever the drive is in run mode.
Setting
b 1 - 0 8 : Run Command Selection
During Program
This parameter determines if the drive will accept a run command while in the "program"
mode. The drive is in the "program" mode whenever the drive light is off.
Setting
5.27
MISCELLANEOUS PROTECTIVE FUNCTIONS
L 8 - 0 1 : Internal Dynamic Braking (Heatsink)
Resistor Protection
Set this parameter to " 1 " only if a heatsink-mount resistor will be used with the drive.
Set L 8 - 0 1 to " 0 " if not using Dynamic Braking, or if using a remote DB resistor.
Setting
L 8 - 0 2 : OH (Overheat) Protection
Alarm Level
This parameter sets the temperature at which the heatsink thermostat will indicate an
overtemperature condition. The corresponding action the drive will take is dependent upon
the setting of L 8 - 0 3 (see below).
L 8 - 0 3 : Operation Selection After OH
(Overheat) Pre-alarm
Setting
0
Timer active whenever power is applied to the drive
1
Timer active whenever drive is in "run" mode
0
Disabled – If a run is commanded while the drive
is in the "program" mode (drive light is off), it will not run.
1
Enabled – If a run is commanded while the drive is in the
"program" mode (drive light off), it will operate normally.
0
Not provided
1
Provided
0
Ramp to Stop (using C1-02 )
1
Coast to Stop (base block)
2
Fast-stop (using C1-09 )
3
Alarm Only (operation continues)
Continued
Factory setting: 0
Range: 0 or 1
Description
Factory setting: 0
Range: 0 or 1
Description
Factory setting: 0
Range: 0 or 1
Description
Factory setting: See Table A3-1
Range: 50 to 130 °C
Factory setting: 3
Range: 0 to 3
Description
5-46