T a b l e A 2 - 1 . S t a n d a r d S p e c i f i c a t i o n s ( C o n t i n u e d )
Input Power
Output Power
NEW DRIVE
OLD DRIVE
MODEL NO.
MODEL NO.
CIMR-G5M
GPD515C-
C003
51P51F
52P21F
C004
C006
53P71F
C010
55P51F
57P51F
C012
C017
50111F
C022
50151F
C027
50181F
50221F
C032
C041
50301F
C052
50371F
50451F
C062
50551F
C077
C099
50751F
C130
50900F
51100F
C172
C200
51600F
( 1 ) Molded-case circuit breaker must be rated for at least 18,000 RMS symmetrical amperes interrupting capacity.
( 2 ) Fuses should be of the current-limiting time-delay type offering protection for semi-conductor devices.
SECTION A. Input Voltage Related
600V Class drive
Voltage : 3 Phase 500/ 575/ 600 VAC +/– 10%
Frequency : 50 / 60 Hz ± 5%
Voltage : 0 - 575V (proportional to input voltage)
Frequency: 0 - 400 Hz (V/Hz pattern selectable)
100% CONT.
RATED
NOMINAL
kVA
HP
2
2
3
3
5
5
7.5
7.5
10
10
15
15
20
20
25
25
30
30
40
40
50
50
60
60
75
75
100
100
125
125
150
150
200
200
RATED
OUTPUT
INPUT
AMPS
AMPS
3.5
4.3
4.1
5.1
6.3
7.7
9.8
12.1
12.5
15.4
17
21
22
28
27
33
32
40
41
51
52
64
62
76
77
95
99
122
130
160
172
211
200
246
A2-2
RECOMMENDED
RECOMMENDED
MCCB
INPUT
RATING
(1)
(AMPS) FUSING (AMPS)
10
10
20
20
20
30
50
60
60
100
100
100
150
225
225
300
400
(2)
10
10
15
25
30
40
50
60
70
100
125
156
200
250
300
400
500