2 . 2 b
P O W E R O N A N D PRELIMINARY CHECKS - FLUX VECTOR CONTROL
• Ensure motor is disconnected from load. To assure safety, disconnect the coupling or
belt which connects the motor with the machine, so that motor operation is isolated
prior to test operation.
• Verify the encoder to be used meets the following criteria: Line driver type (8830,
88C30), output pulse levels of 5-12V, and quadrature (A+, A–, B+, B–). Power supply
for the encoder from the PG-X2 card is capable of 200mA @ 12VDC or 200mA @ 5VDC.
Do not use both of these power supplies simultaneously.
• Verify that the encoder PPR (pulses per revolution) and expected motor speed do not
exceed the bandwidth of the PG-X2 card, using the following formula:
300,000 Hz ≥ 1.2 x (Max Speed in RPM / 60) x PPR of encoder
NOTE: Speed in RPM = 120 x frequency / number of motor poles
Example:
Encoder PPR = 1024, Maximum speed = 1750 RPM
DESCRIPTION
Apply input power to the drive.
If the display is not in English,
go to section 2.3, "CHANGING
THE LANGUAGE ON THE
DIGITAL OPERATOR".
Set the control method of the
drive to Flux Vector (Set
A1-02 to 3.)
300,000 Hz ≥ 1.2 x (1750 / 60) x 1024
300,000 Hz ≥ 35,840 Hz
KEY SEQUENCE
Press
, then
MENU
Press
, then
DATA
ENTER
Press
, then set drive to Flux
DATA
Vector using:
ENTER
Write value to memory by pressing
DATA
ENTER
2-6
Acceptable
DIGITAL OPERATOR DISPLAY
** Main Menu **
twice
Control Method
Open Loop Vector
A1-02=
Entry Accepted
briefly, then
Control Method
Initialize
3
Flux Vector
Flux Vector