Automatic Frequency Regulator (Afr) Gain - Veikong gpd 515/g5 Startup Manual

Simplified startup procedure
Table of Contents

Advertisement

5 . 5
A U T O - R E S T A R T
B .
L 5 - 0 2 : Fault Contact Status During Auto-Restart
This digit controls how the fault contact responds to a drive fault during the auto-restart
operation.
0 = Fault contact will not actuate during auto-restart attempts
1 = Fault contact actuates during auto-restart attempts
FAULT DETECTION
FAULT CONTACT
OUTPUT FREQUENCY
Time from fault detection
to reset attempt, or time
between reset attempts
5 . 6
A U T O M A T I C FREQUENCY REGULATOR (AFR) GAIN
C 8 - 0 8
: AFR Gain
C 8 - 0 9
: AFR Time
Useable only in Open Loop Vector Control Method ( A 1 - 0 2 = 2), these parameters affect
the speed response or prevent the motor from hunting. To improve the speed response,
increase C 8 - 0 8 and/or decrease C 8 - 0 9 . To stop the motor from hunting, decrease
C 8 - 0 8 and/or increase C 8 - 0 9 .
Continued
100 ms
A u to - R e s t a r t O p e r a t i o n T i m i n g
5-8
Factory setting: 0
Range: 0 or 1
L5-01 = 1
L5-01 = 0
MOTOR RPM
AUTOMATIC FAULT RESET
Factory setting: 1 . 0 0
Range: 0.00 to 10.00
Factory setting: 5 0
Range: 0 to 1000
msec