T a b l e 6 - 1 . F a u l t I n d i c a t i o n a n d D e t a i l s – C o n t i n u e d
DIGITAL OPERATOR
DISPLAY
OL2
Inv Overloaded
OL3
Overtorque Det 1
OL4
Overtorque Det 2
OPE01
kVA Selection
OPE02
Limit
OPE03
Terminal
OPE05
Sequence Select
OPE06
PG Opt Missing
OPE07
Analog Selection
OPE08
Terminal
OPE10
V/F Ptrn Setting
OPE11
CarrFrq/ON-Delay
OPR
Oper Disconnect
DESCRIPTION
Drive overload
Overtorque detect 1
Overtorque detect 2
Drive capacity
selection fault
Parameter set out of range
Multi-function input
setting fault
Option card
selection error
PG-X2 card not installed
Multi-function analog
input selection error
Selection Parameter error
V/f data setting fault
Carrier frequency
parameter(s) set out
of range
Operator disconnected
DETAILS
Protects the drive. Drive overload protection has
tripped.
Output current exceeds Overtorque Detection
Level 1 ( L6-02 ).
Output current exceeds Overtorque Detection
Level 2 ( L6-05 ).
o2-04 has been changed from the correct factory
setting value. Refer to Table A3-1.
One or more parameter values are not within the
allowable setting range.
H1-01 thru H1-06 (multi-function input)-2 or
more parameters are set to the same data (other
than " F " and " FF ").
See paragraph 5.32.
Frequency reference and/or run source is set for
option card (b1-01=3 and/or b1-02=3), but no
option card is connected.
Control method set to Flux Vector or V/F with PG,
and no PG-X2 card is installed.
Both multi-function analog inputs (H3-05 and H3-09) have
been programmed for the same data (except 1F) OR an
AI-14B option card is connected, the drive is programmed
for 3-channel individual (F2-01=0), and a multi-function
input is programmed for Option/Inverter Selection (H1-01
to H1-06=2).
A parameter has been changed that is not available
in the present Control Method. Example: H1-08=72
(Zero Servo Command) is set while the drive is in
Flux Vector Control (A1-02=3), then the Control
Method is changed to Open Loop Vector (A1-02=2).
Occurs when the custom V/f pattern does not meet
the following criteria:
( E1-04 ) ≥ ( E1-06 )> ( E1-07 ) ≥ ( E1-09 )
Occurs when the carrier frequency parameters are
set as follows: ( C6-01 ) > 5 kHz and ( C6-02 ) ≤ 5
kHz;( C6-03 ) > 6 and ( C6-01 ) < ( C6-02 )
Digital Operator has been disconnected from drive
while in Run mode.
6-4
TYPE
(Note 1)
M
(Note 2)
(Note 2)
A
A
A
A
A
A
A
A
A
M
(Note 2)