23 Group Drive protection function setting

P23.00
Bus voltage control option
P23.01
Overvoltage stall threshold
P23.02
Undervoltage threshold
P23.03
Overvoltage stall ratio
P23.04
undervoltage stall ratio
Undervoltage trip
P23.05
threshold
Undervoltage fault
P23.06
detecting time
P23.07
Rapidcurrent limit
Over-speed detection
P23.10
value
P23.11
Over-speed detection time
Detection value of too
P23.12
large speed deviation
Detection value of too
P23.13
large speed deviation
Input phase loss
P23.14
detection time
Output phase loss
P23.15
inbalance detecting
Fault protection action
P23.18
selection 1
Unit'digit :Overvoltage stall control
0:overvoltage stall disabled
1:overvoltage stall enabled
2:overvoltage stall self-adjustable
Ten'unit:Undervoltage stall control
0:undervoltage stall disabled
1:undervoltage stall deceleration(decelerate to
zero speed and run at zero speed)
2: undervoltage stall deceleration(decelerate to
zero and stop)
220V Level: 320V~400V
380V Level: 540V~800V
480V Level:650V~950V
690V Level: 950V~1250V
220V level: 160V~300V
380V level: 350V~520V
480V level: 400V~650V
690V level: 650V~900V
0~10.0
0~20.0
220V Level:160V~300V
380V Level:350V~520V
480V Level:400V~650V
660V Level:650V~900V
0.0s~30.0s
0:disabled
1:enabled
0.0%~120.0% maximum frequency
0.0s~30.0s
0.:shielding
0.0%~1P00.0%(motor rated frequency)
0.0s~30.0s
0.0:shielding
0.0s~30.0s
0.0:forbidden
0%~100%
Unit's digit : input phase loss
0: coast to stop
1: Emergent stop
2: Stop as per stop mode
3: continue to Run
- 64 -
Chapter 5 function code table
01
Depend
Depend
1.0
4.0
Depend
1.0s
1
120.0%
1.0s
20.0%
0.0s
8.0s
30%
0000