Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 592

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Processing details
• These instructions store the 16-bit binary data in the device specified by (s) in the (n)th position in the data table in the
device specified by (d). After execution of the FINS(P) instruction, the data after the (n)th position in the data table is moved
down one by one.
(d)
3
(d)+1
5432
(d)+2
1234
(d)+3
-123
(d)+4
0
(d)+5
0
0
(s)
4444
N: Number of data
D
: Data table range (managed by users)
Tr
When (n)=2, data is inserted to the device specified by (d)+2.
• A number from 0 to 65535 is stored in the number of data (d).
Operation error
Error code
Description
(SD0)
3405H
The FINS(P) instruction is executed when the value specified by (n) is 0.
The FINS(P) instruction is executed when the value in the device specified by (d) is FFFFH.
7 APPLICATION INSTRUCTIONS
590
7.5 Data Table Operation Instructions
N
(d)
(d)+1
(d)+2
(d)+3
(d)+4
(d)+5
4
5432
4444
D
Tr
1234
-123
0
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents