10. Peripheral devices

• When supplying power from a wall socket, do not exceed the rated capacity of the socket.
Otherwise, this may generate excessive heat which can start a fire.
Prohibited
• When using switchgear for the inverter, it must be installed in a cabinet.
Failure to do so can lead to risk of electric shock and can result in death or serious injury.
Instruction
• Connect earth cables securely.
Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric
leak.
Prohibited

10.1 Selection of wiring materials and devices

Voltage class
Single-phase
100V class
Single-phase
200V class
Three-phase
200V class
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1,
V/T2 and W/T3 when the length of each wire does not exceed 30m.
The numeric values in parentheses refer to the sizes of wires to be used when a DC reactor is connected.
Note 2: For the control circuit, use shielded wires 0.75 mm
Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: The wire sizes specified in the above table apply to HIV wires (cupper wires shielded with an insulator
with a maximum allowable temperature of 75°C) used at an ambient temperature of 50°C or less.
Note 5: If there is a need to bring the inverter into UL compliance, use wires specified in Chapter 9.
Capacity of
applicable
Inverter model
motor (kW)
compliant
0.1
VFNC3S-1001P
0.2
VFNC3S-1002P
0.4
VFNC3S-1004P
0.75
VFNC3S-1007P
0.1
VFNC3S-2001PL
0.2
VFNC3S-2002PL
0.4
VFNC3S-2004PL
0.75
VFNC3S-2007PL
1.5
VFNC3S-2015PL
2.2
VFNC3S-2022PL
0.1
VFNC3-2001P
0.2
VFNC3-2002P
0.4
VFNC3-2004P
0.75
VFNC3-2007P
1.5
VFNC3-2015P
2.2
VFNC3-2022P
4.0
VFNC3-2037P
Warning
Wire size (See Note 4)
Power circuit
DC reactor
2
(mm
) (Note 1.)
(optional) (mm
For Japan
IEC
IEC
(JEAC800
compliant
1-2005)
1.5
2.0
-
1.5
2.0
-
2.5
2.0
-
4.0
2.0
-
1.5(1.5)
2.0(2.0)
1.5
1.5(1.5)
2.0(2.0)
1.5
1.5(1.5)
2.0(2.0)
1.5
1.5(1.5)
2.0(2.0)
1.5
2.5(2.5)
2.0(2.0)
1.5
4.0(4.0)
2.0(2.0)
1.5
1.5(1.5)
2.0(2.0)
1.5
1.5(1.5)
2.0(2.0)
1.5
1.5(1.5)
2.0(2.0)
1.5
1.5(1.5)
2.0(2.0)
1.5
1.5(1.5)
2.0(2.0)
1.5
2.5(1.5)
2.0(2.0)
1.5
4.0(2.5)
2.0(2.0)
4.0
2
or more in diameter.
J-1
E6581595
Earth cable
2
2
)
(mm
)
For Japan
For Japan
IEC
(JEAC800
(JEAC800
compliant
1-2005)
1-2005)
-
2.5
2.0
-
2.5
2.0
-
2.5
2.0
-
4.0
3.5
2.0
2.5
2.0
2.0
2.5
2.0
2.0
2.5
2.0
2.0
2.5
2.0
2.0
2.5
2.0
2.0
4.0
3.5
2.0
2.5
2.0
2.0
2.5
2.0
2.0
2.5
2.0
2.0
2.5
2.0
2.0
2.5
2.0
2.0
2.5
2.0
2.0
4.0
3.5
10